logo

Guangzhou Xingjin Fire Equipment Co.,Ltd. info@xingjin-fire.com 86--18011936582

Guangzhou Xingjin Fire Equipment Co.,Ltd. Company Profile
products
Home > products > Inert Gas Fire Suppression System > 90L Cylinder 19kg Capacity 15MPa Working Pressure IG541 Inert Gas Fire Suppression System and Inergen Fire Suppression System

90L Cylinder 19kg Capacity 15MPa Working Pressure IG541 Inert Gas Fire Suppression System and Inergen Fire Suppression System

Product Details

Place of Origin: China

Brand Name: Xingjin

Certification: CAL,CMA,CNAS,ILAC-MRA,CCC

Model Number: QMH15/90

Payment & Shipping Terms

Minimum Order Quantity: 2 set system

Price: negotiation

Packaging Details: Plywood outer box with bubble bag or paper

Delivery Time: 10-15 working days

Payment Terms: L/C, D/P, T/T, Western Union, Paypal, Credit card

Supply Ability: 300 sets per month

Get Best Price
Product Details
Highlight:

inergen gas fire suppression system

,

inert gas suppression system

Cylinder Volume:
90L
Capacity:
19kg
Pattern Of Extinguishing:
Enclosed Flooding
Agent:
IG541(52% Nitrogen, 40% Argon, 8% Carbon Dioxide)
Working Pressure:
15MPa
Color:
Red
Cylinder Volume:
90L
Capacity:
19kg
Pattern Of Extinguishing:
Enclosed Flooding
Agent:
IG541(52% Nitrogen, 40% Argon, 8% Carbon Dioxide)
Working Pressure:
15MPa
Color:
Red
Product Description
Product Overview

The IG541 Inert Gas Fire Suppression System is a clean gas fire suppression solution utilizing an IG541 mixture gas composed of 52% nitrogen, 40% argon, and 8% carbon dioxide. This extinguishing agent is colorless, tasteless, non-toxic, and non-conducting, leaving no residue or pollution after discharge. With an Ozone Depletion Potential (ODP) of zero, it is an environmentally friendly gas suitable for extinguishing fires, particularly in locations where electrical fires are likely to occur.

Combined with the extinguishing device and electronic accessories, the entire system can be actuated automatically. It monitors the protected area through detectors and activates the extinguishing device via a solenoid actuator, achieving full automation. This eliminates the risk of an unnoticed fire and reduces the cost of employing personnel to supervise the protected area.

The system also supports management of multiple zones through distributing valves, allowing a single system to protect multiple areas. The agent is discharged only into the zone where the fire occurs, ensuring efficient and rapid fire suppression. A small room should be reserved as storage space for the complete system.

Technical Parameters
No. Specification Technical Parameter
1 Working Pressure 15 MPa
2 Device Model QMH15/80  |  QMH15/90
3 Capacity 80 Ltr  |  90 Ltr
4 Filling Capacity of Gas 16.89 kg  |  19 kg
5 Outside Diameter of Cylinder Φ279 mm  |  Φ325 mm
6 Height of Cylinder 1578+73 mm  |  1345+60 mm
7 Spraying Time ≤120 s
8 Filling Rate 0.211 kg/L
9 Power DC24V / 1.6A
10 Nitrogen Pressure of Driving Device 6.0±1.0 MPa (20°C)
11 Condition of Reserving Room for Container Temperature: 0–50°C
12 Max Working Pressure 17.2 MPa
13 Min Working Pressure 13.6 MPa
Applications

The IG541 Inert Gas Fire Suppression System is suitable for protecting critical facilities and spaces, including:

  • Computer rooms
  • Telecommunication rooms
  • Transformer rooms
  • Electrical switch and distribution rooms
  • Generator rooms
  • Leaching tanks
  • Drying equipment
  • Paint spraying booths
  • Electrical instrument rooms
  • Control centers
  • Libraries and archives
  • Treasure troves of cultural relics
Packaging

Each system is first packed with polyfoam and then placed into a wooden case. Depending on customer requirements or safety regulations, goods can also be secured on a pallet for transport.

IG541 inert gas fire suppression system cylinders packed with polyfoam inside a wooden shipping case
Key Advantages
  • Versatile fire coverage: Suitable for all classes of fire except metal fires, and leaves no residue or pollution after extinguishing.
  • Asset protection: Specifically designed for critical assets and equipment, causing no damage to property. A cost-effective choice for fire suppression.
  • Rapid discharge: The system discharges all agent in under 10 seconds, achieving rapid flooding of the protected area for efficient fire suppression.
  • Built-in evacuation delay: A time-delay mechanism of approximately 2 minutes provides sufficient time to evacuate personnel from the hazardous area when a fire occurs.
  • Multi-zone protection: A single system can protect multiple zones, delivering significant cost savings for large facilities with multiple protected areas.
System Configuration Diagrams
Multiple Cylinders for One Zone
Mimic diagram showing multiple IG541 cylinders connected to protect a single zone
Multiple Cylinders for Multiple Zones
Mimic diagram showing multiple IG541 cylinders with distributing valves protecting multiple separate zones