Home > products > FM200 Gas Suppression System > FM200 Gas Suppression System HFC-227EA Fire Suppression System with 0.95kg/L Filling Rate ≤10s Discharge Time 6.0±1.0MPa Nitrogen Pressure

FM200 Gas Suppression System HFC-227EA Fire Suppression System with 0.95kg/L Filling Rate ≤10s Discharge Time 6.0±1.0MPa Nitrogen Pressure

Product Details

Place of Origin: China

Brand Name: xingjin

Certification: CAL,CMA,CNAS,ILAC-MRA,CCC

Model Number: QMP40/4.2, QMP70/4.2, QMP100/4.2, QMP120/4.2, QMP150/4.2, QMP180/4.2, QMP70/5.6, QMP90/5.6, QMP120/5.6

Payment & Shipping Terms

Minimum Order Quantity: 2 set system

Price: negotiation

Packaging Details: Plywood outer box with bubble bag or paper

Delivery Time: 15-20 working days after payment or receipt of L/C

Payment Terms: T/T, L/C

Supply Ability: 30000 set system

Get Best Price
Product Details
Highlight:

fm 200 suppression system

,

firefighting equipments

,

computer room fm200 system

Nitrogen Pressure Of Driving Device:
6.0±1.0Mpa(20℃)
Spraying Time:
≤10s
Standard Of Examination:
GB25972-2010
Pattern Of Extinguishing:
Enclosed Flooding
Capacity Of Cylinder:
40L, 70L, 90L, 100L, 120L, 150L, 180L
Capacity Of Agent:
38kg, 66.5kg, 85.5kg, 95kg, 114kg, 142.5kg, 171kg
Type:
Pipe Network
Nitrogen Pressure Of Driving Device:
6.0±1.0Mpa(20℃)
Spraying Time:
≤10s
Standard Of Examination:
GB25972-2010
Pattern Of Extinguishing:
Enclosed Flooding
Capacity Of Cylinder:
40L, 70L, 90L, 100L, 120L, 150L, 180L
Capacity Of Agent:
38kg, 66.5kg, 85.5kg, 95kg, 114kg, 142.5kg, 171kg
Type:
Pipe Network
Product Description
System Overview

The FM200 (HFC-227EA) automatic gas fire suppression system is an empty-cylinder solution engineered for total-flooding protection of critical and high-value spaces. It combines extinguishing cylinders, electronic detection accessories, and solenoid actuation to deliver fully automatic fire suppression with zero residue and zero ozone-depletion potential.

Technical Specifications
No. Specification 4.2 MPa System 5.6 MPa System
1 Capacity 40 L, 70 L, 100 L, 120 L, 150 L, 180 L 70 L, 90 L, 120 L
2 Device model QMP40/4.2, QMP70/4.2, QMP100/4.2, QMP120/4.2, QMP150/4.2, QMP180/4.2 QMP70/5.6, QMP90/5.6, QMP120/5.6
3 Filling pressure 4.2 MPa 5.6 MPa
4 Max. filling rate 0.95 kg/L 1.08 kg/L
5 Discharge time ≤ 10 s
6 Power supply DC 24 V / 1.6 A
7 Nitrogen driving device 6.0 ± 1.0 MPa
8 Storage surroundings Temperature: −10 to 50 °C; relative humidity: ≤ 97%
9 Proportion (protected area) ≤ 800 m²
10 Volume (protected space) ≤ 3600 m³
FM200 gas suppression system cylinder and valve assembly with specification markings
Product Description

FM200 (HFC-227EA) is a colorless, odorless, non-corrosive, and electrically insulating extinguishing gas that leaves no residue or pollution after discharge. Its ODP is zero, making it an environmentally friendly extinguishing agent. These properties allow it to be used safely in special locations where electrical fires are likely to occur.

Combined with the extinguishing device and electronic accessories, the entire system can be actuated automatically. It monitors the protected area through detectors and triggers the extinguishing device via a solenoid actuator, achieving full automation. This eliminates the risk of an unnoticed fire and reduces the cost of personnel required to supervise the protected area.

The system also supports management of multiple zones under a single safe control scheme. Using selective valves, one system can protect several zones and direct the agent to the zone where a fire occurs, ensuring fast and efficient extinguishing. A small room should be reserved as storage space for the system components.

Applications

The system is suitable for protecting critical and high-value environments, including:

  • Electronic computer rooms and data processing centers
  • Telecommunications facilities and process control rooms
  • Expensive medical equipment and industrial equipment
  • Libraries, museums, and art galleries
  • Clean rooms and emergency power facilities
  • Flammable liquid storage areas

It is also well suited to locations where fire is likely to occur, such as:

  • Paint-spraying production lines and aging-electrical equipment
  • Rolling machines, printing machines, and oil switches
  • Oil-immersed transformers and melt-impregnating tanks
  • Large generators and drying equipment
  • Cement production processes involving pulverized coal
  • Ship engine rooms and cargo holds
Working Principle

The diagram below illustrates the working principle of the complete system, from detection and control through agent release.

Schematic diagram illustrating the working principle of the FM200 gas fire suppression system, including detectors, control panel, solenoid actuator, and discharge network
System working principle diagram