30MPa Working Pressure 80L Cylinder Volume Enclosed Flooding Inert Gas Fire Suppression System and Nitrogen Fire Extinguishing System

Product Details

Place of Origin: China

Brand Name: Xingjin

Certification: CAL,CMA,CNAS,ILAC-MRA,CCC

Model Number: QMD30/80, QMD30/140

Payment & Shipping Terms

Minimum Order Quantity: 2 set system

Price: negotiation

Packaging Details: Plywood outer box with bubble bag or paper

Delivery Time: 10-15 working days

Payment Terms: L/C, D/P, T/T, Western Union, Paypal, Credit card

Supply Ability: 300 sets per month

Get Best Price
Product Details
Highlight:

Nitrogen inert gas suppression system

,

inert gas suppression system 80l

,

inert gas suppression system 140l

Cylinder Volume:
80L, 140L
Pattern Of Extinguishing:
Enclosed Flooding
Agent:
IG100(100% Pressurized Nitrogen)
Working Pressure:
30MPa
Max. Working Pressure:
36.6MPa
Min. Working Pressure:
27MPa
Color:
Red
Capacity Of Agent:
24.7 Kg, 43.2 Kg
Cylinder Volume:
80L, 140L
Pattern Of Extinguishing:
Enclosed Flooding
Agent:
IG100(100% Pressurized Nitrogen)
Working Pressure:
30MPa
Max. Working Pressure:
36.6MPa
Min. Working Pressure:
27MPa
Color:
Red
Capacity Of Agent:
24.7 Kg, 43.2 Kg
Product Description
Inert Gas Nitrogen Fire Extinguishing System

The Inert Gas IG-100 Fire Suppression System is available with cylinder volumes of 80L and 140L, designed for enclosed flooding applications. IG-100 uses nitrogen for a clean, safe, and 100% ecological extinguishing solution. This gas is widely used across a variety of extinguishing systems due to its excellent pressurization conditions.

The system achieves equal smothering efficiency by reducing the oxygen concentration to extinguish the fire, while leaving a percentage of oxygen suitable for occupied areas. Because of this feature, personnel can be protected where there is a possibility they may be in the enclosure area at the time of a fire, ensuring safe evacuation both in terms of the oxygen level in the room and the absence of chemicals in the discharge. In addition, its physical and dispersion properties help maintain visibility during evacuation.

Technical Parameters
No. Specification Technical Parameter
1 Working Pressure 30 MPa
2 Device Model QMD30/80  |  QMD30/140
3 Cylinder Volume 80 Ltr  |  140 Ltr
4 Filling Capacity of Gas 24.7 kg  |  43.2 kg
5 Outside Diameter of Cylinder Φ267 mm  |  Φ356 mm
6 Height of Cylinder 1770 mm ±10 mm  |  1825 mm ±20 mm
7 Spraying Time ≤120 s
8 Filling Rate (@200 bar) 0.31 kg/L
9 Power DC24V / 1.6A
10 Nitrogen Pressure of Driving Device 6.0 ±1.0 MPa (20℃)
11 Condition of Reserving Room for Container Temperature: 0~50℃
12 Max. Working Pressure 36.6 MPa
13 Min. Working Pressure 27 MPa
System Components

The complete system includes the following components:

  • Storage cylinder group and storage cylinder group frame
  • Nitrogen driving device and nitrogen driving device frame
  • Cylinder valve
  • Liquid flow check valve and air flow check valve
  • Electromagnetic starter
  • Gas conveying pipeline and collecting pipe
  • Choice valve, three links, reducer tee, and reducing elbow
  • Flange, safety valve, and pressure transmitter
  • Pipes and nozzles
  • Chemicals
  • Fire detector and fire controller
  • Sound and light alarm, alarm bell, and gas light
  • Emergency start / stop button
Typical Applications

The following are typical hazards protected by INERGEN systems:

  • Computer rooms
  • Subfloors
  • Tape storage
  • Telecommunications / switchgear rooms
  • Vaults
  • Process equipment
  • All normally occupied or unoccupied areas where electronic equipment is either very sensitive or irreplaceable
Packaging

We always pack the system with polyfoam first and then place it into a wooden case. Sometimes, to meet customer or safety requirements, we will make a pallet for the goods.

Inert gas nitrogen fire extinguishing system cylinders packed with polyfoam inside a wooden shipping case
Key Advantages
  • Compared with the traditional 15 MPa system, the number of fire extinguishing agent cylinders can be reduced by 25%–50%.
  • The building area between cylinders is effectively reduced, improving the overall occupation and utilization rate of the building.
  • Constant 6 MPa low-pressure release can reduce the cost of pipelines and pipe fittings.
  • The constant release pressure of 6 MPa provides more lasting and effective pressure, with a transmission distance of up to 200 meters.
  • Low-pressure release of the whole system has less impact on on-site personnel, equipment, and building structure, making it safer.
  • The external constant-pressure reliever only bears pressure when the system is spraying, which is convenient for disassembly and maintenance and effectively reduces the failure rate of the system.
  • After spraying, the system does not need to replace any parts; with simple disassembly and secondary filling, the system can be quickly put back into operation.
  • The opening area of the pressure-relief device is reduced, directly lowering the input cost of the pressure-relief device, and the safety buckle is installed and arranged more simply.
  • The nitrogen fire extinguishing system (IG-100) can be widely used to make rapid response to fire, protect on-site staff, address sudden fires, and protect important places sensitive to chemical reactions, effectively safeguarding personnel and property.
Mimic Diagram
Multiple Cylinders for Multiple Zones
Mimic diagram showing multiple nitrogen cylinders configured to protect multiple separate fire zones
Multiple Cylinders for One Zone
Mimic diagram showing multiple nitrogen cylinders manifolded together to protect a single fire zone