Guangzhou Xingjin Fire Equipment Co.,Ltd. info@xingjin-fire.com 86--18011936582
Product Details
Place of Origin: Guangzhou,China
Brand Name: XINGJIN
Certification: CCC,CAC,ROHS
Model Number: HTFC
Payment & Shipping Terms
Minimum Order Quantity: 5 set
Price: Pricing based on quantity
Packaging Details: Wooden Box Or Plywood Outer Box With Bubble Bag Or Paper
Delivery Time: According to product quantity
Payment Terms: T/T, L/C
Supply Ability: 30000set/month
Fan Type: |
Axial Flow Fire Smoke Exhaust Fan |
Customized Support: |
OEM, ODM |
Mounting Type: |
Duct Fan |
Blade Material: |
Aluminum |
Warranty: |
2YEAR |
Maximum Operating Temperature: |
280℃ |
Installation: |
Vertical, Horizontal, Hanging |
Speed: |
450-1200r/min |
Power: |
0.55-45KW |
Color: |
Blue; White;Customized Colors |
Model Specifications: |
HTFC-9;HTFC-10;HTFC-12... |
Fan Type: |
Axial Flow Fire Smoke Exhaust Fan |
Customized Support: |
OEM, ODM |
Mounting Type: |
Duct Fan |
Blade Material: |
Aluminum |
Warranty: |
2YEAR |
Maximum Operating Temperature: |
280℃ |
Installation: |
Vertical, Horizontal, Hanging |
Speed: |
450-1200r/min |
Power: |
0.55-45KW |
Color: |
Blue; White;Customized Colors |
Model Specifications: |
HTFC-9;HTFC-10;HTFC-12... |
HTFC-I centrifugal fire smoke exhaust fan
Introduction:
The HTFC series dual-purpose, low-noise centrifugal fume cabinet for fire smoke exhaust (ventilation) is designed and manufactured by our company by absorbing advanced domestic and international technologies and integrating our years of meticulous fume cabinet research to optimize fan performance, including pressure and air volume. This latest product offers multiple functions for both ventilation and fire smoke exhaust. It has passed inspection by the National Fire Equipment Quality Testing Center and complies with the GA211-1999 Fire Smoke Exhaust Fan Test Method and JB/TI0218-2001 Fire Smoke Exhaust Fan Technical Requirements. It has also received China's mandatory 3C certification. It has demonstrated normal operation at a medium temperature of 280°C for more than 30 minutes, complying with GB50045 (Code for Fire Protection Design of High-Rise Civil Buildings).
Applicable scenarios:
This fan is suitable for use in venues requiring ventilation and fire smoke exhaust, such as stadiums, exhibition centers, hotels, office buildings, theaters, auditoriums, hospitals, shopping malls, high-rise residential buildings, basements (parking lots), factories and mines, and indoor spaces in large buildings.
Model parameters:
Model (NO) |
Power (KW) |
Speed (r/min) |
Flow (m/h) |
Pressure (Pa) |
Noise dB(A) | ![]() |
HTFC-9 |
0.55 | 900 | 2581-3703 | 195-174 | ≤58 | |
0.75 | 1000 | 2540-4233 | 255-273 | ≤62 | ||
1.1 | 1100 | 2876-4753 | 306-316 | ≤63 | ||
1.5 | 1200 | 3126-5049 | 367-372 | ≤66 | ||
HTFC-10 |
0.55 | 800 | 2484-3703 | 199-212 | ≤62 | |
0.75 | 900 | 2718-4113 | 255-270 | ≤64 | ||
1.1 | 1000 | 3040-4692 | 300-332 | ≤66 | ||
1.5 | 1100 | 3437-5 528 | 384-393 | ≤68 | ||
2.2 | 1200 | 3582-5877 | 431-454 | ≤70 | ||
HTFC-12 |
0.75 | 700 | 3599-5710 | 243-249 | ≤59 | |
1.1 | 800 | 4102-6355 | 308-318 | ≤61 | ||
1.5 | 900 | 4877-7176 | 386-394 | ≤65 | ||
2.2 | 1000 | 5123-7939 | 473-479 | ≤67 | ||
3 | 1100 | 5674-8818 | 571-578 | ≤69 | ||
HTFC-15 |
1.5 | 700 | 6179-9698 | 352-364 | ≤61 | |
2.2 | 800 | 6953-11164 | 457-479 | ≤64 | ||
3 | 850 | 7293-11810 | 510-532 | ≤65 | ||
4 | 900 | 7645-12337 | 569-595 | ≤67 | ||
5.5 | 1000 | 8466-14156 | 701-734 | ≤70 | ||
HTFC-18 |
2.2 | 600 | 8288-12595 | 352-357 | ≤60 | |
3 | 700 | 9170-15329 | 463-474 | ≤62 | ||
4 | 750 | 10319-16325 | 532-549 | ≤64 | ||
5.5 | 800 | 11176-17557 | 601-617 | ≤65 | ||
7.5 | 900 | 12208-19434 | 753-768 | ≤74 | ||
HTFC-20 |
3 | 550 | 10660-16150 | 329-378 | ≤60 | |
4 | 600 | 11739-17557 | 390-449 | ≤62 | ||
5.5 | 650 | 12607-19084 | 457-522 | ≤64 | ||
7.5 | 700 | 13533-20454 | 529-606 | ≤66 | ||
11 | 800 | 15399-24114 | 680-778 | ≤69 | ||
HTFC-22 |
4 | 550 | 13311-20255 | 362-402 | ≤60 | |
5.5 | 600 | 14964-22894 | 405-476 | ≤62 | ||
7.5 | 650 | 6009-23774 | 482-552 | ≤65 | ||
11 | 700 | 17205-25756 | 563-645 | ≤66 | ||
15 | 800 | 20032-29932 | 733-827 | ≤69 | ||
HTFC-25 |
5.5 | 500 | 20055-29932 | 381-413 | ≤67 | |
7.5 | 550 | 21968-32736 | 456-495 | ≤67 | ||
11 | 600 | 23960-35270 | 531-589 | ≤70 | ||
15 | 650 | 26084-38823 | 632-682 | ≤73 | ||
18.5 | 700 | 28161-42190 | 713-785 | |||
HTFC-28 |
7.5 | 450 | 25369-35270 | 390-413 | ≤65 | |
11 | 500 | 27716-39879 | 472-509 | ≤68 | ||
15 | 550 | 31199-43481 | 562-606 | ≤70 | ||
18.5 | 600 | 33604-47610 | 665-726 | ≤72 | ||
22 | 650 | 36607-51457 | 782-854 | ≤75 | ||
HTEC-30 |
11 | 400 | 28172-41700 | 368-390 | ≤76 | |
15 | 450 | 31551-45838 | 458-492 | ≤79 | ||
18.5 | 500 | 35903-51762 | 568-601 | ≤81 | ||
22 | 550 | 36665-56360 | 675-720 | ≤84 | ||
30 | 600 | 40900-63315 | 805-854 | ≤86 | ||
HTFC-33
|
15 | 400 | 40783-61087 | 425 -462 | ||
18.5 | 450 | 44923-68852 | 536-577 | ≤81 | ||
22 | 500 | 49638-76549 | 657-708 | ≤83 | ||
30 | 550 | 54659-84406 | 792-852 | ≤85 | ||
37 | 600 | 60641-91866 | 929-1004 | ≤88 | ||
|
18.5 | 400 | 45127-69056 | 436-486 | ||
22 | 450 | 64505-77309 | 553--622 | ≤83 | ||
30 | 500 | 1023-87294 | 670-742 | ≤84 | ||
37 | 550 | 77707-110827 | 789-898 | ≤86 | ||
45 | 600 | 111947-120452 | 940-1073 | ≤88 |