Place of Origin: Guangzhou,China

Brand Name: XINGJIN

Certification: GSG\TUV\ I S O 9 0 0 1, 1 4 0 0 1, 4 5 0 0 1

Model Number: Novec 1230

Payment & Shipping Terms

Minimum Order Quantity: 10 set system

Price: Pricing based on quantity

Packaging Details: Wooden Box Or Plywood Outer Box With Bubble Bag Or Paper

Delivery Time: 15-20days

Payment Terms: T/T, L/C

Supply Ability: 30000set/month

Get Best Price
Product Details
Highlight:
Filling Pressure:
4.2Mpa/5.6Mpa
Scale Of Protective Region For One Zone:
Area:max Single-zone Is 800m² Volume: Max Single-zone Is 3600m³
Spraying Time:
≤10s
Filling Density:
≤950kg/m3,≤1080kg/m3
Power:
DC24V/1.6A
Nitrogen Pressure Of Driving De Vice:
6.0±1.0Mpa(20℃)
Condition Of Reserving Room For Container:
Temperature: -10~50℃, Relative Humidity: ≤97%
Max Working Pressure:
5.3Mpa/8.0Mpa
Min Working Pressure:
4.2Mpa/4.6Mpa
Filling Pressure:
4.2Mpa/5.6Mpa
Scale Of Protective Region For One Zone:
Area:max Single-zone Is 800m² Volume: Max Single-zone Is 3600m³
Spraying Time:
≤10s
Filling Density:
≤950kg/m3,≤1080kg/m3
Power:
DC24V/1.6A
Nitrogen Pressure Of Driving De Vice:
6.0±1.0Mpa(20℃)
Condition Of Reserving Room For Container:
Temperature: -10~50℃, Relative Humidity: ≤97%
Max Working Pressure:
5.3Mpa/8.0Mpa
Min Working Pressure:
4.2Mpa/4.6Mpa
Product Description

Pipe Network Type Of Novec1230 Automatic Fire Suppression System


Description:

  Novec1230 fluid offers a unique combination of safety, low environmental impact and extinguishing performance, making it the only chemical halon replacement to offer a viable, long-term, environmentally sustainable technology for special hazards fire protection.

 

Applications:




  Electronic computer room, a data processing center, telecommunications facilities, process control, expensive medical equipment, industrial equipment, library, museum and art gallery, clean room, an echoic chamber, emergency power facilities, flammable liquid storage area, etc.
 

  The place where the fire is easy to happen, like paint-spraying production line, aging-electrical equipment, rolling machine, printing machine, oil switch, oil immersed transformer, melt impregnating tank, tank, large generators, drying equipment, cement production process of pulverized coal, and the ship's engine room, cargo hold, etc.




 

Novec1230 Clean Agent Gas Fire Suppression System with Fast 10 Second Pipe Network Discharge 0


 

Compositions:
  Pipe network type of Novec1230 automatic fire suppression system is mainly composed by three parts. Extinguishing devices and pipe fittings and electrical accessories.

  Extinguishing devices are such things, like cylinder to fill and store Novec1230, frame and driving device(nitrogen cylinder) to trigger the storage cylinder to discharge agent and so on.

  Pipe fittings are those conduits to connect extinguishing device and guide agent into protective zone, like high pressure galvanized steel pipe and flange and elbow and so on.

  Electrical accessories are those things which are used to detect and monitor whole protective area and control whole system, also warn people to evacuate and prevent from fire expansion.

  These integrated three parts will be efficient to detect and supervise and alarm and extinguish fire automatically.
  Here attached below is complete composition of whole system,

 

Novec1230 Clean Agent Gas Fire Suppression System with Fast 10 Second Pipe Network Discharge 1

Single/multiple cylinders for multiple zones

Novec1230 Clean Agent Gas Fire Suppression System with Fast 10 Second Pipe Network Discharge 2

Multiple cylinders for one zone

Novec1230 Clean Agent Gas Fire Suppression System with Fast 10 Second Pipe Network Discharge 3

Single cylinder for one zone


 

Parameter:

No. specification Technical Parameter
1 Filling pressure 4.2Mpa 5.6Mpa
2 Scale of Protective region for one zone area:max single-zone is 800m² volume: max single-zone is 3600m³
3 Spraying time ≤10s
4 Filling density ≤950kg/m3 ≤1080kg/m3
5 power DC24V/1.6A
6

Nitrogen Pressure of Driving De

vice

6.0±1.0Mpa(20℃)
7

Condition of reserving room for

container

temperature: -10~50℃, relative humidity: ≤97%
8 max working pressure 5.3Mpa 8.0Mpa
9 min working pressure 4.2Mpa 4.6Mpa