Guangzhou Xingjin Fire Equipment Co.,Ltd. info@xingjin-fire.com 86--18011936582
Product Details
Place of Origin: China
Brand Name: xingjin
Certification: CAL,CMA,CNAS,ILAC-MRA,CCC
Payment & Shipping Terms
Minimum Order Quantity: 2 set system
Price: negotiation
Packaging Details: Plywood outer box with bubble bag or paper
Delivery Time: 15-20 working days after payment or receipt of L/C
Payment Terms: T/T, L/C
Supply Ability: 30000 set system
Pattern Of Extinguishing: |
Enclosed Flooding |
Capacity Of Cylinder: |
120L |
Nitrogen Pressure Of Driving Device: |
6.0±1.0Mpa(20℃) |
Power: |
DC24V/1.6A |
Agent: |
Hfc227ea |
Storage Pressure: |
4.2Mpa |
Pattern Of Extinguishing: |
Enclosed Flooding |
Capacity Of Cylinder: |
120L |
Nitrogen Pressure Of Driving Device: |
6.0±1.0Mpa(20℃) |
Power: |
DC24V/1.6A |
Agent: |
Hfc227ea |
Storage Pressure: |
4.2Mpa |
| No. | Specification | Technical Parameter |
|---|---|---|
| 1 | Filling pressure | 4.2 MPa |
| 2 | Scale of protective region for one zone | Area: max single-zone is 800 m²; Volume: max single-zone is 3600 m³ |
| 3 | Spraying time | ≤ 10 s |
| 4 | Filling density | ≤ 950 kg/m³ |
| 5 | Power | DC 24 V / 1.6 A |
| 6 | Nitrogen pressure of driving device | 6.0 ± 1.0 MPa (at 20 °C) |
| 7 | Condition of reserving room for container | Temperature: −10 to 50 °C; Relative humidity: ≤ 97% |
| 8 | Max working pressure | 5.3 MPa |
| 9 | Min working pressure | 4.2 MPa |
FM200 (HFC-227ea) is a colorless, tasteless, non-corrosive, and electrically insulating gas that leaves no residue or pollution after extinguishing. Its Ozone Depletion Potential (ODP) is zero, making it an environmentally friendly extinguishing agent. Because of these properties, it is particularly suitable for locations where electrical fires are likely to occur.
Combined with the extinguishing device and electronic accessories, the entire system can be actuated automatically. It monitors the protective region through detectors and can start the extinguishing device via a solenoid actuator automatically, achieving full automation. This eliminates the risk of an unnoticed fire and reduces the cost of employing personnel to supervise the protected area.
Management of multiple zones is also safely handled by the system. A single system can protect multiple zones through selective valves, allowing the system to target different protective zones alternately. The agent is discharged directly into the zone where the fire occurs, ensuring efficient fire suppression in a short time. Note that a small room should be reserved as storage space for the entire system.
Suitable for electronic computer rooms, data processing centers, telecommunications facilities, process control rooms, expensive medical equipment, industrial equipment, libraries, museums and art galleries, clean rooms, anechoic chambers, emergency power facilities, and flammable liquid storage areas.
Also ideal for locations where fires are likely to occur, such as paint-spraying production lines, aging electrical equipment, rolling machines, printing machines, oil switches, oil-immersed transformers, melt impregnating tanks, large generators, drying equipment, cement production processes involving pulverized coal, and ship engine rooms and cargo holds.
The 4.2 MPa FM200 suppression system with 120 L storage cylinders is mainly composed of three parts: extinguishing devices, pipe fittings, and electrical accessories.
These three integrated parts work together to efficiently detect, supervise, alarm, and extinguish fires automatically.