Product Details:
|
|
Place of Origin: | China |
---|---|
Brand Name: | xingjin |
Certification: | CAL,CMA,CNAS,ILAC-MRA,CCC |
Payment & Shipping Terms:
|
|
Minimum Order Quantity: | 1set system |
Price: | negotiation |
Packaging Details: | Plywood case,Paper carton |
Delivery Time: | 10-15 working days after payment or receipt of L/C |
Payment Terms: | L/C, T/T, D/P, Western Union,Paypal,Credit Card,Debit Card |
Supply Ability: | 3,00 set per month |
Detail Information |
|||
Dimension(mm): | 550*450*1650 | Capacity Of Cylinder: | 90L |
---|---|---|---|
Standard Of Examination: | GB25972-2010 | Pattern Of Extinguishing: | Enclosed Flooding |
Weight: | 50kg | Actuation: | Automatic Or Manual |
High Light: | gas fm 200,auto fire suppression system,90l cabinet type fm200 system |
Product Description
90L Cabinet Type Hfc-227ea FM200 Fire Extinguishing System
Description:
1. Electric insulation, utilization for extinguishing of electrical combustion
2. No residue and pollution inside protection zone
3. No need for employment of monitor staff
4. Short time discharge of extinguishing agent
5. Preparation for storage room
6. Agent quantity for biggest zone is enough to protect all zones through selector valves
Applications:
Electronic computer room, a data processing center, telecommunications facilities, process control, expensive medical equipment, industrial equipment, library, museum and art gallery, clean room, anechoic chamber, emergency power facilities, flammable liquid storage area, etc.
The place where the fire is easy to happen, like paint-spraying production line, aging-electrical equipment, rolling machine, printing machine, oil switch, oil immersed transformer, melt impregnating tank, tank, large generators, drying equipment, cement pro duction process of pulverized coal, and the ship's engine room, cargo hold, etc.
Parameter:
No. | specification | Technical Parameter |
1 | Filling pressure | 2.5Mpa |
2 | Relief pressure | 5.0±0.225Mpa |
3 | Spraying time | ≤10s |
4 | Working temperature | 0~50℃ |
5 | Power | DC24V/1.6A |
6 | max working pressure | 4.2Mpa |
Compositions:
90L cabinet type Fm200 System is mainly composed by two parts. Extinguishing devices and electrical accessories.
Extinguishing devices are such things, like cabinet to store extinguishing device, cylinder to fill and store fm200 and flexible hose and solenoid actuator and so on.
Electrical accessories are those things which are used to detect and monitor whole protective area and control whole system, also warn people to evacuate and prevent from fire expansion.
These integrated two parts will be efficient to detect and supervise and alarm and extinguish fire automatically.
Attention:
1. One cabinet or multiple cabinet type fm200 for one zone
2. Enough space in protective region to place it, such as corner or edge of wall
3. Attention to compare height of cabinet and room
Advantages:
The cabinet type fm200 fire suppression system has a lot of advantages, and here is going to show users some of its strong points.
1/ Convenient installation. Compared with pipe network system, cabinet system would be relatively simple to conduct installation. After installation of control panels and electric components, left work is just to connect it with one cabinet fire extinguishing device or devices. But one room should not be matched with more than 4 pieces of it because of the limitation of the output current of a control panel.
2/ Lower cost. Obviously, the price would be cheaper than pipe network type for the protection zone which just needs one single cylinder, because there is no need to consider about the expense of pipes and pipe fittings, also the cost of manpower for this part.