The fire extinguishing agent release time for the FM200 pipe network system is typically controlled within ≤ 10 seconds.
Protective areas such as communication rooms and computer rooms: The design discharge time should not exceed 8 seconds.
Other protection zones (such as the power distribution room, archives, etc.): The design discharge time should not exceed 10 seconds.
To ensure rapid establishment of the fire suppression concentration
FM200 is a total flooding gas fire suppression system. It requires the establishment of a sufficient fire suppression concentration (typically 8%-10%) within the protected area at the early stage of the fire to extinguish the fire. If the discharge time is too long, the fire may have already spread and expanded, and the fire suppression effect will be greatly reduced.
Prevent the risk of fire reignition
The rapid spray can enable the fire extinguishing agent to quickly cover the fire source at the early stage of the fire, effectively suppressing the combustion chain reaction and preventing the fire from reigniting.
Reduce the hazards of thermal decomposition products
When FM200 is exposed to high-temperature flames, it will decompose and produce a small amount of hydrogen fluoride gas. The shorter the spray duration, the shorter the contact time between the fire extinguishing agent and the flame, and the lower the amount of decomposition products generated, resulting in a smaller potential impact on equipment and personnel.
International standard collaboration
The NFPA 2001 (Standard for Clean Gas Fire Extinguishing Systems of the American Fire Protection Association) and ISO 14520 and other international standards all have similar regulations regarding the discharge time, ensuring the international universality of the system design.
Yes, the FM200 pipeline system has a delay release time before startup, usually ranging from 0 to 60 seconds (adjustable).
| Purpose of Delay | Specific Description |
|---|---|
| Personnel Safe Evacuation | Before system activation, audible and visual alarms will sound to alert personnel in the protected area to evacuate immediately. The delay time provides the necessary time window for personnel to safely evacuate. |
| Shutdown of Interlocked Equipment | Before the extinguishing agent is released, the system needs to interlock and shut down air conditioning, ventilation systems, fire dampers and other equipment in the protected area to prevent loss of extinguishing agent and ensure the area is sealed. |
| False Alarm Confirmation & Emergency Stop | If the fire detector triggers a false alarm or personnel determine that activation is unnecessary, the emergency stop button can be pressed during the delay time to avoid unnecessary agent discharge and property loss. |
| Compliance Requirements | According to GB 50263-2007 Code for Installation and Acceptance of Gas Fire Extinguishing Systems, gas fire extinguishing systems must be equipped with a delayed start device to ensure personnel safety. |