Guangzhou Xingjin Fire Equipment Co.,Ltd. info@xingjin-fire.com 86--18011936582
Product Details
Place of Origin: China
Brand Name: Xingjin
Certification: CAL,CMA,CNAS,ILAC-MRA,CCC
Model Number: QMH15/80, QMH15/90
Payment & Shipping Terms
Minimum Order Quantity: 2 set system
Price: negotiation
Packaging Details: Plywood outer box with bubble bag or paper
Delivery Time: 10-15 working days
Payment Terms: L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability: 300 sets per month
Cylinder Volume: |
80L, 90L |
Capacity: |
14.25kg, 16.04kg |
Pattern Of Extinguishing: |
Enclosed Flooding |
Agent: |
IG100 (100% Pressurized Nitrogen) |
Working Prussure: |
15MPa |
Color: |
Red |
Cylinder Volume: |
80L, 90L |
Capacity: |
14.25kg, 16.04kg |
Pattern Of Extinguishing: |
Enclosed Flooding |
Agent: |
IG100 (100% Pressurized Nitrogen) |
Working Prussure: |
15MPa |
Color: |
Red |
Description of Fire extinguishing agent
A form of fire suppression system that employs nitrogen gas to put out fires is the IG100 nitrogen fire suppression system, commonly referred to as an inert gas fire suppression system. As an inert gas that prevents burning, nitrogen is suitable for usage in populated spaces.
The normal operation of the IG100 system is described as follows:
Nitrogen Release: Nitrogen gas is released into the protected area via the IG100 system. Through a system of pipes or distribution nozzles, the nitrogen gas is released into the space after being kept in high-pressure cylinders or tanks.
Nitrogen Gas Displaces Oxygen: As the nitrogen gas is released, it quickly fills the enclosed space and dilutes the oxygen. The amount of oxygen in the air is decreased to a point where prolonged combustion is impossible, effectively putting out the fire.
Fire Extinguishment: The IG100 system eliminates the oxygen that the fire need to burn by lowering the oxygen content. As a result, the fire can no longer maintain itself, which causes it to be put out.
Limited Residue: The nitrogen gas utilized in the IG100 system discharges with no residue, which reduces the amount of cleanup and restoration work necessary following a fire occurrence. This is especially advantageous in delicate settings where water or chemical residue could result in further harm, such as data centers or museums.
The IG100 system is commonly used in areas where water-based fire suppression systems may cause significant damage, such as electrical equipment rooms, data centers, archives, museums, and other facilities with valuable equipment or sensitive materials.
It's important to note that the IG100 system should be designed, installed, and maintained by qualified professionals following applicable regulations and standards. The system's design should consider factors such as room volume, fire load, and ventilation to ensure proper fire suppression effectiveness. Regular inspections and maintenance are necessary to ensure the system remains in optimal working condition and to address any potential issues that may arise.
Parameters of Fire Suppression System
No. | Specification | Technical Parameter | |
1 | Working Pressure | 15Mpa | |
2 | Device Model | QMD15/80 | QMD15/90 |
3 | Capacity | 80Ltr | 90Ltr |
4 | Filling Capacity of Gas | 14.25kg | 16.04kg |
5 | Outside Diameter of Cylinder | Φ279mm | Φ325mm |
6 | Height of Cylinder | 1578+73mm | 1345+60mm |
7 | Spraying Time | ≤10s | |
8 | Max Filling Rate | 0.178kg/L | |
9 | Power | DC24V/1.6A | |
10 | Nitrogen Pressure of Driving Device | 6.0±1.0Mpa(20℃) | |
11 | Condition of Reserving Room for Container | temperature: 0~50℃ | |
12 | Max Working Pressure | 17.2Mpa | |
13 | Min Working Pressure | 13.6Mpa |
Application of Fire Suppression System
Fire suppression systems are designed to detect, contain, and extinguish fires in buildings, vehicles, and other enclosed spaces. Here are some common applications of fire suppression systems:
In general, fire suppression systems are crucial for preventing the disastrous impacts of fires on people and property. To make sure they'll work in an emergency, they should be installed and maintained by trained experts. To achieve the highest level of safety, fire suppression systems should be utilized in conjunction with fire preventive strategies including routine fire drills, smoke detectors, and fire extinguishers.
Advantages
When compared to the standard 15MPa system, the number of fire extinguishing agent cylinders may be reduced by 25% to 50%.
A constant 6MPa low pressure release can lower the cost of pipeline and pipe fittings.
Packages
We always place it into a wooden case after first packing it with polyfoam. At times, we will create a pallet for the goods in order to satisfy clients or meet safety requirements.
Mimic Diagram
Single/Multiple cylinder(s) for multiple zone
Single/Multiple cylinder(s) for one zone
After-Sale Service
• We have an efficient sales and after sales team to promise slove all client's question in time.
• We provide 8×6 hrs technical support and service.