Guangzhou Xingjin Fire Equipment Co.,Ltd. info@xingjin-fire.com 86--18011936582
Product Details
Place of Origin: Guangzhou,China
Brand Name: XINGJIN
Certification: GSG\TUV\GB6653-2008
Model Number: WZ-Q/T-QZ3-XJ60
Payment & Shipping Terms
Minimum Order Quantity: 100 set system
Price: Pricing based on quantity
Packaging Details: Wooden Box Or Plywood Outer Box With Bubble Bag Or Paper
Delivery Time: 15-20days
Payment Terms: T/T,L/C
Supply Ability: 30000set/month
Maximum Loading Factor: |
0.6kg/L |
Melting Point Temperature: |
170℃±10℃ |
Operating Temperature Range: |
(0~49)℃ |
Maximum Tube Length: |
25m |
Nominal Working Pressure: |
5.7Mpa |
Maximum Loading Factor: |
0.6kg/L |
Melting Point Temperature: |
170℃±10℃ |
Operating Temperature Range: |
(0~49)℃ |
Maximum Tube Length: |
25m |
Nominal Working Pressure: |
5.7Mpa |
The CO2 fire detection tube system is an innovative fixed non-electric self-actuating fire suppression device that combines fire detection and extinguishing functions into a single flexible tube. Unlike traditional gas systems, it requires no power supply, no complex detectors, no control panels, and no intricate piping networks – making it ideal for protecting enclosed electrical cabinets, control panels, and compact equipment spaces where conventional systems cannot be installed.
The fire detection tube is made of specialized polymer material with an outer diameter of 6mm, inner diameter of 4mm, and wall thickness of 1.0mm±0.1mm. When a fire occurs, the tube bursts at the point of highest temperature (170±10°C), releasing pressure and activating the container valve. The extinguishing agent is then discharged directly through the burst opening (direct type) or through dedicated nozzles (indirect type), delivering targeted fire suppression within seconds.![]()
Direct Type vs Indirect Type Configuration Comparison:
| Parameter | Direct Type | Indirect Type |
|---|---|---|
| Protected Volume | ≤10m³ | ≤100m³ |
| Agent Charge Weight | 6kg | 45kg |
| Min. Agent Required per Unit | 2.5kg/m³ | 1.5kg/m³ |
| Max. Detection Tube Length | 25m | 25m |
| Max. Release Tube Length | — | 12m |
Key Technical Specifications:
Working Pressure: 5.7MPa; Max Working Pressure: 12.1MPa
Max Filling Rate: 0.6kg/L
Operating Temperature Range: 0~49°C![]()