Guangzhou Xingjin Fire Equipment Co.,Ltd. info@xingjin-fire.com 86--18011936582
Product Details
Place of Origin: Guangdong, China
Brand Name: Xingjin
Certification: CAL, CMA, CNAS, ILAC-MRA, CCC
Model Number: QMQ4.2/90-XJ-3M30D
Payment & Shipping Terms
Minimum Order Quantity: 2 sets
Price: USD 1,900 - 2,700 / Set
Packaging Details: Plywood case with bubble bag and moisture barrier film, export standard
Delivery Time: 15-20 working days after deposit or L/C receipt
Payment Terms: T/T,L/C,Western Union
Supply Ability: 400 sets per Month
Agent: |
HFC-227ea / FM200 |
Cylinder Volume: |
90L (40L-180L Optional) |
Filling Pressure: |
4.2 MPa At 20 C |
Filling Density: |
950 Kg/m3 Or Less |
Actuation Modes: |
Automatic, Electrical Manual, Mechanical Emergency Manual |
Time Delay: |
0-30 Seconds, Adjustable |
Discharge Time: |
10 Seconds Or Less After Delay |
Protected Volume: |
Up To 3600 M3 |
Power Supply: |
DC 24V / 1.6A |
Alarm Devices: |
Sounder And Strobe, Pre-discharge Warning |
Working Temperature: |
-10 C To +50 C |
Agent: |
HFC-227ea / FM200 |
Cylinder Volume: |
90L (40L-180L Optional) |
Filling Pressure: |
4.2 MPa At 20 C |
Filling Density: |
950 Kg/m3 Or Less |
Actuation Modes: |
Automatic, Electrical Manual, Mechanical Emergency Manual |
Time Delay: |
0-30 Seconds, Adjustable |
Discharge Time: |
10 Seconds Or Less After Delay |
Protected Volume: |
Up To 3600 M3 |
Power Supply: |
DC 24V / 1.6A |
Alarm Devices: |
Sounder And Strobe, Pre-discharge Warning |
Working Temperature: |
-10 C To +50 C |
A total flooding HFC-227ea system that gives people time to leave before the agent is released. Three independent actuation paths are combined with a 0–30 second adjustable delay, so the alarm sounds, the countdown runs, and discharge only starts after the evacuation window you set.
![]()
![]()
![]()
| Mode | How it works | When it is used |
|---|---|---|
| Automatic | Detector logic confirms fire, panel starts the delay countdown, then releases the agent | Unmanned rooms, data centres, night operation |
| Electrical manual | Release push button outside the protected room, protected against accidental operation | Staff present at the panel when fire is confirmed |
| Mechanical emergency manual | Direct lever on the cylinder valve, works without power or control panel | Power failure, panel damage, emergency override |
| Parameter | Specification |
|---|---|
| Agent | HFC-227ea / FM200 clean agent |
| Cylinder volume | 90L (40L, 70L, 100L, 120L, 150L, 180L available) |
| Filling pressure | 4.2 MPa at 20 °C |
| Filling density | ≤950 kg/m³ |
| Actuation modes | Automatic, electrical manual, mechanical emergency manual |
| Time delay | 0–30 seconds, adjustable |
| Discharge time | ≤10 seconds after delay |
| Protected volume | Up to 3600 m³ |
| Power supply | DC 24V / 1.6A |
| Alarm devices | Sounder and strobe, pre-discharge warning |
| Working temperature | -10 °C to +50 °C |
| Certification | CAL, CMA, CNAS, ILAC-MRA, CCC |
Data centres, telecommunication rooms, electrical switch rooms, control rooms, archives, museum stores, laboratories and other occupiable spaces where staff may be inside the protected room at the moment of alarm.
Seamless steel cylinder with HFC-227ea charge, cylinder valve with solenoid and mechanical lever, flexible discharge hose, pipe network and nozzles, control panel with delay and abort functions, smoke and heat detectors, sounder and strobe, warning plate and installation manual. Cylinder volume, delay range and zone count can be configured to the project.