Guangzhou Xingjin Fire Equipment Co.,Ltd. info@xingjin-fire.com 86--18011936582
Product Details
Place of Origin: Guangdong, China
Brand Name: Xingjin
Certification: CAL, CMA, CNAS, ILAC-MRA, CCC
Model Number: QMQ4.2/120-XJ-NR
Payment & Shipping Terms
Minimum Order Quantity: 2 sets
Price: USD 2,050 - 2,900 / Set
Packaging Details: Plywood case with bubble bag and moisture barrier film, nozzles packed separately
Delivery Time: 15-20 working days after deposit or L/C receipt
Payment Terms: T/T,L/C,Western Union
Supply Ability: 400 sets per Month
Agent: |
HFC-227ea / FM200 |
Cylinder Volume: |
120L (40L-180L Optional) |
Filling Pressure: |
4.2 MPa At 20 C |
Filling Density: |
950 Kg/m3 Or Less |
Discharge Time: |
10 Seconds Or Less |
Protected Volume: |
Up To 3600 M3 |
Actuation Modes: |
Automatic, Electrical Manual, Mechanical Emergency Manual |
Residue: |
None, Ventilation Only After Discharge |
Electrical Conductivity: |
Non-conductive Agent |
Ozone Depletion Potential: |
Zero |
Working Temperature: |
-10 C To +50 C |
Agent: |
HFC-227ea / FM200 |
Cylinder Volume: |
120L (40L-180L Optional) |
Filling Pressure: |
4.2 MPa At 20 C |
Filling Density: |
950 Kg/m3 Or Less |
Discharge Time: |
10 Seconds Or Less |
Protected Volume: |
Up To 3600 M3 |
Actuation Modes: |
Automatic, Electrical Manual, Mechanical Emergency Manual |
Residue: |
None, Ventilation Only After Discharge |
Electrical Conductivity: |
Non-conductive Agent |
Ozone Depletion Potential: |
Zero |
Working Temperature: |
-10 C To +50 C |
HFC-227ea discharges as a colourless, electrically non-conductive gas and turns back into gas before it settles. Nothing is left on circuit boards, optics, sensors or calibration references, so the room is usable again as soon as it is ventilated – no powder clean-up, no water damage, no oily film to wipe off.
![]()
![]()
| Item | HFC-227ea clean agent | Dry powder | Water / sprinkler |
|---|---|---|---|
| Residue | None | Abrasive dust | Water and corrosion |
| Effect on electronics | Non-conductive, safe | Dust in fans and drives | Short circuit risk |
| Clean-up after discharge | Ventilation only | Full room cleaning | Drying and replacement |
| Downtime | Hours | Days to weeks | Days |
| Secondary damage | None expected | High | High |
| Parameter | Specification |
|---|---|
| Agent | HFC-227ea / FM200 clean agent |
| Cylinder volume | 120L (40L, 70L, 90L, 100L, 150L, 180L available) |
| Filling pressure | 4.2 MPa at 20 °C |
| Filling density | ≤950 kg/m³ |
| Discharge time | ≤10 seconds |
| Protected volume | Up to 3600 m³ |
| Actuation | Automatic, electrical manual, mechanical emergency manual |
| Power supply | DC 24V / 1.6A |
| Nozzle type | Balanced pipe network with 360° nozzles |
| Ozone depletion potential | Zero |
| Working temperature | -10 °C to +50 °C |
| Certification | CAL, CMA, CNAS, ILAC-MRA, CCC |
Server and storage racks, MRI and CT suites, laboratory analysers, semiconductor test benches, calibration and metrology rooms, control and instrumentation cabinets, broadcasting and editing suites, and archive media stores.
We calculate agent quantity from room volume, enclosure leakage and design concentration, then lay out nozzles so the agent reaches blind corners, raised floors and cable voids within the discharge time. Drawings and filling records are supplied for project approval.
Seamless steel cylinder with HFC-227ea charge, cylinder valve, flexible discharge hose, pipe network and nozzles, control panel, smoke and heat detectors, sounder and strobe, warning plate and installation manual. Volume, nozzle layout and control logic can be configured to the room drawing.