Zero Residue HFC 227ea Fire Extinguishing System with 120L Cylinder for Precision Equipment Protection

Product Details

Place of Origin: Guangdong, China

Brand Name: Xingjin

Certification: CAL, CMA, CNAS, ILAC-MRA, CCC

Model Number: QMQ4.2/120-XJ-NR

Payment & Shipping Terms

Minimum Order Quantity: 2 sets

Price: USD 2,050 - 2,900 / Set

Packaging Details: Plywood case with bubble bag and moisture barrier film, nozzles packed separately

Delivery Time: 15-20 working days after deposit or L/C receipt

Payment Terms: T/T,L/C,Western Union

Supply Ability: 400 sets per Month

Get Best Price
Product Details
Highlight:

Zero Residue HFC 227ea Fire Extinguishing System

,

120L Cylinder FM200 Fire Suppression System

,

Precision Equipment Clean Agent Fire Extinguishing System

Agent:
HFC-227ea / FM200
Cylinder Volume:
120L (40L-180L Optional)
Filling Pressure:
4.2 MPa At 20 C
Filling Density:
950 Kg/m3 Or Less
Discharge Time:
10 Seconds Or Less
Protected Volume:
Up To 3600 M3
Actuation Modes:
Automatic, Electrical Manual, Mechanical Emergency Manual
Residue:
None, Ventilation Only After Discharge
Electrical Conductivity:
Non-conductive Agent
Ozone Depletion Potential:
Zero
Working Temperature:
-10 C To +50 C
Agent:
HFC-227ea / FM200
Cylinder Volume:
120L (40L-180L Optional)
Filling Pressure:
4.2 MPa At 20 C
Filling Density:
950 Kg/m3 Or Less
Discharge Time:
10 Seconds Or Less
Protected Volume:
Up To 3600 M3
Actuation Modes:
Automatic, Electrical Manual, Mechanical Emergency Manual
Residue:
None, Ventilation Only After Discharge
Electrical Conductivity:
Non-conductive Agent
Ozone Depletion Potential:
Zero
Working Temperature:
-10 C To +50 C
Product Description

Clean Agent, Zero Residue – HFC 227ea Fire Extinguishing System for Precision Equipment

HFC-227ea discharges as a colourless, electrically non-conductive gas and turns back into gas before it settles. Nothing is left on circuit boards, optics, sensors or calibration references, so the room is usable again as soon as it is ventilated – no powder clean-up, no water damage, no oily film to wipe off.

Zero Residue HFC 227ea Fire Extinguishing System with 120L Cylinder for Precision Equipment ProtectionZero Residue HFC 227ea Fire Extinguishing System with 120L Cylinder for Precision Equipment Protection

What “No Residue” Means in Practice

  • No powder: dry chemical agents leave abrasive dust that migrates into fans, disk drives and optical paths.
  • No water: sprinkler and water mist systems cause short circuits, corrosion and warped media.
  • No oily film: the agent is stored and discharged as a gas, so no liquid carrier reaches the surfaces.
  • Non-conductive: suitable for energised electrical and electronic equipment.
  • Fast return to service: after ventilation the room meets design concentration limits again, and equipment can be restarted without cleaning.

Agent Comparison for Equipment Rooms

Item HFC-227ea clean agent Dry powder Water / sprinkler
Residue None Abrasive dust Water and corrosion
Effect on electronics Non-conductive, safe Dust in fans and drives Short circuit risk
Clean-up after discharge Ventilation only Full room cleaning Drying and replacement
Downtime Hours Days to weeks Days
Secondary damage None expected High High

Technical Specifications

Parameter Specification
Agent HFC-227ea / FM200 clean agent
Cylinder volume 120L (40L, 70L, 90L, 100L, 150L, 180L available)
Filling pressure 4.2 MPa at 20 °C
Filling density ≤950 kg/m³
Discharge time ≤10 seconds
Protected volume Up to 3600 m³
Actuation Automatic, electrical manual, mechanical emergency manual
Power supply DC 24V / 1.6A
Nozzle type Balanced pipe network with 360° nozzles
Ozone depletion potential Zero
Working temperature -10 °C to +50 °C
Certification CAL, CMA, CNAS, ILAC-MRA, CCC

Precision Equipment It Protects

Server and storage racks, MRI and CT suites, laboratory analysers, semiconductor test benches, calibration and metrology rooms, control and instrumentation cabinets, broadcasting and editing suites, and archive media stores.

Engineering Support

We calculate agent quantity from room volume, enclosure leakage and design concentration, then lay out nozzles so the agent reaches blind corners, raised floors and cable voids within the discharge time. Drawings and filling records are supplied for project approval.

Scope of Supply

Seamless steel cylinder with HFC-227ea charge, cylinder valve, flexible discharge hose, pipe network and nozzles, control panel, smoke and heat detectors, sounder and strobe, warning plate and installation manual. Volume, nozzle layout and control logic can be configured to the room drawing.