IG55 20MPa Piping Network for Inert Gas Fire Suppression System - Non-Toxic & Safe with Long Transmission Distance

Product Details

Place of Origin: Guangzhou, Guangdong, China

Brand Name: Guangzhou Xingjin Fire Equipment Co.,Ltd.

Certification: ilac-MRA, ISO9001:2008

Model Number: QMDY 30/80,QMDY 30/140

Payment & Shipping Terms

Minimum Order Quantity: 1 set system

Price: Negotiation

Packaging Details: Wooden Box Or Plywood Outer Box With Bubble Bag Or Paper

Delivery Time: According to product quantity

Payment Terms: L/C,T/T

Supply Ability: 30000set/month

Get Best Price
Product Details
Highlight:

IG55 inert gas fire suppression system

,

20MPa fire suppression piping network

,

inert gas system piping with warranty

Storage Pressure:
30MPa
Maximum Working Pressure (+50℃):
36.6MPa
Minimum Working Pressure (0℃):
27MPa
Container Capacity:
80L
Maximum Filling Volume:
34.06kg
System Operating Voltage:
220V AC,24V DC
System Startup Mode:
Electrical Automatic, Electrical Manual, Mechanical Emergency Start
Storage Pressure:
30MPa
Maximum Working Pressure (+50℃):
36.6MPa
Minimum Working Pressure (0℃):
27MPa
Container Capacity:
80L
Maximum Filling Volume:
34.06kg
System Operating Voltage:
220V AC,24V DC
System Startup Mode:
Electrical Automatic, Electrical Manual, Mechanical Emergency Start
Product Description

The IG55 20MPa piping network is the core delivery channel for the inert gas fire suppression system, specifically designed for IG55 mixed gas (50% nitrogen + 50% argon) at 20MPa working pressure. It safely and efficiently transports the extinguishing agent from the cylinder assembly to each nozzle within the protected area, making it widely used in commercial facilities such as data centers, telecommunication rooms, electrical switchgear rooms, and industrial facilities for gas fire protection projects.
IG55 20MPa Piping Network for Inert Gas Fire Suppression System - Non-Toxic & Safe with Long Transmission Distance

Product Overview

IG55 is a blend of nitrogen and argon in equal proportions, classified as a naturally occurring inert gas. It is colorless, odorless, non-toxic, non-conductive, and produces no chemical decomposition by-products. The fire extinguishing principle of IG55 is to reduce the oxygen concentration in the protected area to below 15%, achieving smothering fire suppression. It has zero ozone depletion potential and zero global warming potential. The IG55 20MPa piping network serves as the agent delivery system, consisting of seamless steel pipes, manifolds, selector valves, check valves, flexible hoses, and piping accessories. The system ensures that the extinguishing agent is delivered accurately to each protected zone within the required time frame, with a transmission distance of up to 200 meters.

Specification

Technical Parameter

Working Pressure

20MPa

Device Model

QMDY 20/80

QMDY 20/140

Cylinder Volume

80Ltr

140Ltr

Filling Capacity of Gas

22.9 kg

40.1 kg

Outside Diameter of Cylinder

Φ279mm

Φ356mm

Height of Cylinder

1610mm±70mm

1825mm±20mm

Spraying Time

≤120s

Filling Rate (@200 bar)

0.286kg/L

Power

DC24V/1.6A

Nitrogen Pressure of Driving Device

6.0±1.0MPa(20℃)

Condition of Reserving Room for Container

temperature:  0~50℃

Max. working pressure

23.2 MPa

Min. working pressure

18 MPa

Applicable Places

The IG55 20MPa piping network system is suitable for the following commercial and industrial applications:

  • Data Centers & Server Rooms – Protects critical IT equipment with zero residue and no hardware damage; piping layout is flexible for raised floors and suspended ceilings

  • Telecommunication Rooms & Base Stations – Suitable for occupied spaces; agent is non-toxic and safe; piping covers multiple equipment areas

  • Electrical Switchgear & Distribution Rooms – Protects high-voltage electrical equipment; IG55 is non-conductive with no impact on electrical insulation

  • Generator Rooms – Suitable for diesel generator fire protection; the piping system supports automatic activation

  • Museums & Archives – No corrosion or contamination to valuable artifacts, artwork, or paper documents; the piping system enables independent protection for multiple zones

  • Control Centers & Instrument Rooms – Protects precision control equipment with zero residue, ensuring business continuity

  • Libraries & Cultural Relic Repositories – Agent causes no damage to paper collections; no extensive cleanup required after discharge

  • Industrial Facilities – Oil immersion tanks, drying equipment, paint spray booths, and other high-risk areas; piping meets high-pressure delivery requirements
    IG55 20MPa Piping Network for Inert Gas Fire Suppression System - Non-Toxic & Safe with Long Transmission DistanceIG55 20MPa Piping Network for Inert Gas Fire Suppression System - Non-Toxic & Safe with Long Transmission DistanceIG55 20MPa Piping Network for Inert Gas Fire Suppression System - Non-Toxic & Safe with Long Transmission Distance

Product Advantages

  • 20MPa Efficient Storage – Saves 25%-50% of cylinder quantity compared to traditional 15MPa systems, significantly reducing cylinder room footprint and improving building utilization

  • Constant 6MPa Low-Pressure Discharge – Reduces piping and component costs; minimal impact on site personnel, equipment, and building structure for enhanced safety

  • Long Transmission Distance – Constant 6MPa discharge pressure provides durable and effective transmission capability up to 200 meters, allowing centralized cylinder room placement

  • Non-Toxic & Safe – IG55 consists of natural atmospheric components, completely harmless to humans and suitable for occupied spaces; no toxic decomposition by-products during fire extinguishing

  • Clean & Environmentally Friendly – ODP = 0, GWP = 0, leaves no residue and causes no pollution to equipment or the environment; meets international green building standards

  • Easy Maintenance – No core component replacement required after system discharge; simple disassembly and refill allows quick return to service

  • Reduced Project Costs – Smaller gas pressure relief opening area reduces safety relief device costs; simpler installation and arrangement

  • Flexible Combined Distribution – A single IG55 20MPa piping network can protect multiple zones with selector valves for zone control

  • Rapid Response – Widely applicable to facilities requiring fast fire response; effectively protects personnel and property safety
    IG55 20MPa Piping Network for Inert Gas Fire Suppression System - Non-Toxic & Safe with Long Transmission DistanceIG55 20MPa Piping Network for Inert Gas Fire Suppression System - Non-Toxic & Safe with Long Transmission Distance

Core Piping Components



Component Function Description
Agent Cylinder Assembly 80L/140L steel cylinders filled with IG55 agent at 20MPa working pressure
Container Valve Seals the cylinder; features both pneumatic and manual activation
Manifold Collects agent from multiple cylinders and delivers to the main pipeline
Selector Valve Enables combined distribution; directs agent to designated zones
Check Valve Prevents agent backflow and ensures stable system pressure
Flexible Hose Connects cylinders to the manifold; absorbs high-pressure discharge impact
Pressure Reducing Device Reduces high-pressure agent to constant 6MPa discharge pressure
Pilot Gas Cylinder 4L/10L nitrogen cylinder provides power for container valve activation
Solenoid Actuator DC24V driven; automatically activates upon receiving fire alarm signal
Pressure Feedback Device Sends signal to alarm controller upon agent discharge
Low Leakage High Seal Valve Prevents system misactivation caused by pilot line leakage
Pipes & Brackets High-pressure galvanized seamless steel pipes with standard brackets

Technical Specifications



Parameter Specification
Working Pressure 20MPa (storage)
Maximum Working Pressure 23.2MPa
Minimum Working Pressure 18MPa
Discharge Pressure Constant 6MPa
Cylinder Capacity 80L / 140L
Filling Capacity 22.9kg (80L) / 40.1kg (140L)
Filling Density 0.286kg/L
Spraying Time ≤120 seconds
Pilot Gas Pressure 6.0±1.0MPa (20℃)
System Operating Voltage DC24V / 1.6A
Cylinder Room Temperature 0℃~50℃
Transmission Distance Up to 200 meters
Applicable Standard GB25972-2010

System Working Principle

When a fire occurs in the protected zone, the fire detector sends a signal to the alarm control panel, which activates audible and visual alarms and closes ventilation and air conditioning equipment. After a 30-second time delay, the controller outputs a DC24V activation signal, energizing the solenoid actuator to open the pilot gas cylinder, releasing nitrogen. The nitrogen passes through the pilot line to activate the pneumatic actuator, puncturing the container valve diaphragm and opening the container valve. The agent flows through the flexible hose into the manifold, is directed by the selector valve to the corresponding protected zone piping network, and is finally discharged from the nozzles to extinguish the fire.

The system is equipped with three independent activation modes – automatic, electrical manual, and mechanical emergency – ensuring reliable operation under all conditions.